 VSP Home : Variances : Potable Water
 

5.7.1.1.3 Potable Water - Denied

 
Request:
Exemption from installing backflow prevention devices on the international shore connection(s) for the fire suppression system(s).
 
VSP Operations Manual Requirement:
5.7.1.1.3 The vessel shall provide a comprehensive cross-connection control program that provides safe connections to the potable water system through air gaps or appropriate backflow devices for specified locations aboard the ship including the international shore connection.
 
Denied:
Backflow prevention devices on the international shore connections for the fire suppression systems are required to protect the shoreside water system.  This system is connected to the ship and other ships during emergency situations that may be bunkering water from the same system at that time.  This variance was denied because not using a backflow prevention device puts other water systems at risk of becoming contaminated.
 
Requesters: Date:
American Canadian Cruise Line 2002
Imperial Majesty 2002
 
 

 

 

   