Control of Exposure to Perchloroethylene in Commercial Dry Cleaning by Ventilation

Perchloroethylene (PERC) is the most commonly used dry cleaning solvent. PERC can enter the body through respiratory and dermal exposure.
Symptoms associated with PERC exposure include: depression of the central nervous system; damage to the liver and kidneys; impaired memory; confusion; dizziness; headache; drowsiness; and eye, nose and throat irritation. Repeated dermal exposure may result in dry, scaly and fissured dermatitis.
VENTILATION

Ventilation should be used to control worker exposure to PERC and ensure thermal comfort. Both measures are important in drycleaning shops. Control techniques that eliminate or reduce PERC exposure by capturing vapors should be used first. Ventilation does not eliminate vapors; rather, it can prevent vapors from reaching the worker's breathing zone. Ventilation control should be accomplished by capturing and removing the contaminant at or near the source (local ventilation), or diluting the concentration of the contaminant before it reaches the worker’s breathing zone (general ventilation).

LOCAL EXHAUST VENTILATION (LEV)

LEV captures the vapor at or near its source of release. This ventilation technique reduces the vapor level reaching the worker's breathing zone and minimizes vapor diffusion. Vapor diffusion is one cause of background ambient air PERC concentrations throughout the shop. In dry cleaning shops, the release of PERC vapors into the environment and subsequent worker exposure to PERC vapors is greatest during machine maintenance and loading and unloading. Dry cleaning machines that use LEV as a control should have an inward air velocity of 100 fpm through the loading and unloading door (known as the door's face velocity). This velocity helps reduce solvent vapors escaping into the shop by providing a draft of clean air passing over the items being removed from the machine. Exhaust from the machine should be ducted to a point 5 ft above the roof to prevent reentry to the work environment or entry to adjacent establishments. LEV systems are typically activated by a door interlocking switch.

An alternative for older machines without built-in exhaust ventilation is to retrofit an external ventilation hood outside the machine door. Airflow capacity in cfm through this retrofit hood should not be less than 100 times the door opening area in square feet (i.e., a 4 ft2 door opening would need an exhaust hood flow rate at least 400 cfm). The exhaust hood should be isolated from cross drafts caused by general ventilation, floor or other shop fans, and high personnel traffic areas.

GENERAL VENTILATION

General ventilation, also known as dilution ventilation, should be used to supply conditioned fresh air and to exhaust contaminated air from the general workroom area. This ventilation technique can provide temperature control and reduce background levels of PERC in the dry cleaning shop. Generally accepted guidelines recommend an air change in the workroom every 5 min with a minimum of 30 cfm of outside air per person. Supply and exhaust systems within the shop should move air from a clean area (offices, customer counters, etc.) to a less clean area (where the dry cleaning machine is located). This process reduces movement of contaminated air into other areas of the shop. Exhaust fans should pull fresh air through the dry cleaning area, drawing vapors away from the workers. Make-up air, which replaces the air exhausted to the outside, enters naturally through windows and doors or through large fans in the ceiling or walls. Insufficient volumes of make-up air could cause an outward flow of contaminated air from the dry cleaning area. A qualified ventilation system contractor should be contacted to assist with this work.

EMERGENCY VENTILATION

Emergency ventilation systems should be available to control solvent vapors if a solvent spill or leak occurs.
Figure 1

Figure 1

Figure 2

Figure 2
201-11A; 201-12A; 201-13A; 201-13B; 201-14A; 201-15A; 201-16A; 201-17A; 201-18A; 201-19A; 240-11; 240-12; 240-13; 240-14; 240-15; 256-16B; 256-17B; 256-18B; 256-19B;
NIOSH [1997]. NIOSH Report: Control of health and safety hazards in commercial drycleaners: chemical exposures, fire hazards, and ergonomic risk factors. Cincinnati, OH: U.S. Department of Health and Human Services, Centers for Disease Control and Prevention. DHHS (NIOSH) Publication No. 97-150.