|
|
| Name of school: |
| Date of inspection: |
| Career-Technical program/course/room: |
| Signature of inspector: |
![]() |
Fire
Protection and Prevention
for Construction Self-Inspection Checklist |
![]()
Guidelines: This checklist covers selected construction regulations issued by the U.S. Department of Labor, Occupational Safety and Health Administration (OSHA) under 29 CFR 1926. It applies to temporary worksites associated with construction, alteration, demolition, and repair including painting and decorating. Fixed facilities, such as Career-Technical educational classrooms, are not covered by the construction regulations. This checklist covers fire protection and prevention for construction sites. The regulations cited apply only to private employers and their employees, unless adopted by a State agency and applied to other groups such as public employees. A yes answer to a question indicates that this portion of the inspection complies with the OSHA or U.S. Environmental Protection Agency (EPA) standard, or with a nonregulatory recommendation.
| Please Circle | |
| General Requirements | |
all times at construction sites? [29 CFR 1926.150(a)(2)] |
Y N N/A ?? |
at construction sites? [29 CFR 1926.150(a)(3)] |
Y N N/A ?? |
and maintained in operating condition at construction sites? [29 CFR 1926.150(a)(4)] |
Y N N/A ?? |
a 55-gallon open drum of water with two fire pails provided for each 3,000 square feet of protected building area? [29 CFR 1926.150(c)(1)(i) and (ii)] |
Y N N/A ?? |
or drum of water 100 feet or less? [29 CFR 1926.150(c)(1)(i)] Note:
A 1/2-inch diameter garden-type hose
|
Y N N/A ?? |
less than 2A, provided on each floor? [29 CFR 1926.150(c)(1)(iv)] |
Y N N/A ?? |
is at least one fire extinguisher located adjacent to the stairway? [29 CFR 1926.150(c)(1)(iv)] |
Y N N/A ?? |
protected from freezing? [29 CFR 1926.150(c)(1)(v)] |
Y N N/A ?? |
combustible liquids or 5 pounds of flammable gas are present, is a fire extinguisher, rated not less than 10B, provided within 50 feet? [29 CFR 1926.150(c)(1)(vi)] Note:
This requirement does not apply to
|
Y N N/A ?? |
according to the classes of anticipated fires and size and degree of hazards? [29 CFR 1926.150(c)(1)(x) and N.J.A.C. 5:18-3.4(f)1] |
Y N N/A ?? |
| Fire Prevention | |
located so that the exhausts are well away from combustible materials? [29 CFR 1926.151(a)(2)] |
Y N N/A ?? |
piped outside the building under construction, is a clearance of at least 6 inches maintained between such piping and combustible material? [29 CFR 1926.151(a)(2)] |
Y N N/A ?? |
materials are piled? Are piles lower than 20 feet? [29 CFR 1926.151(c)(1)] |
Y N N/A ?? |
procedure provided for the periodic cleanup of the entire area? [29 CFR 1926.151(c)(3)] |
Y N N/A ?? |
than 10 feet from a building or structure? [29 CFR 1926.151(c)(5)] |
Y N N/A ?? |
obstruct or adversely affect the means of exit? [29 CFR 1926.151(d)(1)] |
Y N N/A ?? |
minimize the spread of fire and permit convenient access for firefighting? [29 CFR 1926.151(d)(2),(3),(4)] |
Y N N/A ?? |
at least 36 inches is maintained between the top level of stored materials and the sprinkler deflectors? [29 CFR 1926.151(d)(5)] |
Y N N/A ?? |
and heating units to prevent ignition of combustible materials? [29 CFR 1926.151 (d)(6)] |
Y N N/A ?? |
around the path of travel of fire doors, unless a barricade is provided? [29 CFR 1926.151 (d)(7)] |
Y N N/A ?? |
from a fire door opening? [29 CFR 1926.151(d)(7)] |
Y N N/A ?? |
| Temporary Heating Devices | |
flammable and combustible materials? [29 CFR 1926.154(b)(1),(2),(3),(4)] |
Y N N/A ?? |
![]()
Comments/Corrective action:
|
|
|
|