Ventilation of funeral home preparation rooms: guidelines and calculations.

Authors
New Jersey Department of Health and Senior Services (NJDHSS), Public Health Services Branch, Division of Epidemiology, Environmental and Occupational Health, Environmental and Occupational Health Service, Environmental & Occupational Health Surveillance Program
Source
Trenton, NJ: New Jersey Department of Health and Senior Services (NJDHSS), 2006 Jan; :1-2
NIOSHTIC No.
20043730
Abstract
VENTILATION GUIDELINES: Ventilation requirements for funeral home preparation rooms are not specifically addressed in current existing guidelines. However, the National Mechanical Code of the Building Officials and Code Administrators (BOCA) and the Heating, Ventilation, and Air-Conditioning Handbook of the American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) specify ventilation criteria for autopsy rooms. These criteria for autopsy rooms can serve as useful guidelines for effectively ventilating funeral home preparation rooms. BOCA requires a minimum of 12 air changes per hour for autopsy rooms. The BOCA Code also requires that the air shall be exhausted to the outdoors, at an approved location on the exterior of the building. ASHRAE recommends a minimum of 12 air changes per hour be supplied to autopsy rooms, and that at least two of the air changes per hour be outdoor air. ASHRAE also specifies that the room be negatively pressurized in relation to adjacent areas. The New Jersey Funeral Directors Association recommends, as an accepted industry practice, 10-15 air changes per hour for preparation rooms. A source of makeup air should also be provided in preparation rooms to prevent excessive negative pressurization and to improve air mixing within the room.
Keywords
Respiratory-system-disorders; Respiration; Pulmonary-system; Pulmonary-system-disorders; Pulmonary-function; Diseases; Bronchial-asthma; Humans; Men; Women; Public-health; Risk-factors; Employee-exposure; Employees; Employee-health; Ventilation; Air-flow; Air-monitoring; Air-quality
Publication Date
20060101
Document Type
Other
Funding Type
Cooperative Agreement
Fiscal Year
2006
Identifying No.
Cooperative-Agreement-Number-U60-OH-008338; Cooperative-Agreement-Number-U60-CCU-208160
Source Name
Ventilation of funeral home preparation rooms: guidelines and calculations
State
NJ
Performing Organization
New Jersey Department of Health and Senior Services
Page last reviewed: May 11, 2023
Content source: National Institute for Occupational Safety and Health Education and Information Division