Health hazard evaluation report: evaluation of environmental controls at a homeless shelter (City Rescue Mission--New Life Inn) associated with a tuberculosis outbreak - Florida.

Martin-SB Jr.; Mead-KR; Lawrence-RB; Beaty-MC
Morgantown, WV: U.S. Department of Health and Human Services, Public Health Service, Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health, HETA 2012-0155-3180, 2013 Jul; :1-32
In May 2012, the National Institute for Occupational Safety and Health (NIOSH) received a request for technical assistance from the Duval County Health Department as part of its response to an ongoing tuberculosis (TB) outbreak among homeless persons in Florida. The request asked NIOSH to assess heating, ventilation, and air-conditioning (HVAC) systems and make recommendations to improve overall environmental controls at four homeless facilities with epidemiologic links to past or ongoing TB disease transmission. During an on-site evaluation of the City Rescue Mission-New Life Inn homeless shelter in August 2012, we collected physical and ventilation measurements in all key areas of the facility. We focused on areas where shelter guests typically congregate or spend significant amounts of time. We recorded the make and model number of all air-handling units (AHUs) providing supply air to the facility, and visually inspected the units. When possible, we measured the air flow rate through supply diffusers and return grilles. The ventilation systems in place could have contributed to airborne disease transmission among shelter guests. With the exception of condensate leakage from a few AHUs, the units appeared sufficiently maintained to be fully operational. Unfortunately, none of the AHUs provided fresh outdoor air to the occupied spaces, as required by the Florida Building Code and the American Society of Heating, Refrigerating and Air-Conditioning Engineers design standards. In addition to alleviating odors and maintaining occupant comfort, outdoor air serves to dilute infectious aerosols, such as Mycobacterium tuberculosis droplet nuclei that are responsible for TB transmission. Since the TB outbreak began, City Rescue Mission-New Life Inn has taken numerous steps to improve administrative controls, particularly when it comes to identifying guests showing signs and symptoms of TB. We recommend additional improvements to the administrative and environmental controls at the shelter. From a ventilation standpoint, we suggest that all occupied spaces in the shelter are supplied adequate amounts of outdoor air. In addition, we identified areas that could be converted for use as respiratory separation areas. These spaces could serve to separate guests suspected of having TB or other respiratory diseases from the remainder of the guest population, until medical evaluation or treatment could be obtained. We also recommend developing a written infection control plan, HVAC operation and maintenance plan, and a written respiratory protection program. Having these plans/programs in place will help the shelter under normal operating conditions, and especially during future outbreaks of respiratory disease.
Infectious-diseases; Infection-control; Respiratory-system-disorders; Bacteria; Bacterial-disease; Bacterial-infections; Region-4; Ventilation; Ventilation-systems; Heating-equipment; Heating-systems; Air-conditioning-equipment; Air-contamination; Indoor-air-pollution; Indoor-environmental-quality; Disease-transmission; Disease-control; Disease-prevention; Environmental-control-equipment; Environmental-engineering; Environmental-exposure; Engineering-controls; Control-technology; Air-flow; Measurement-equipment; Airborne-particles; Equipment-design; Air-quality; Aerosols; Administration; Humans; Sociological-factors; Quality-standards; Respiratory-protection; Public-health; Author Keywords: Temporary Shelters; tuberculosis; environmental controls; ventilation; homeless shelter; airborne infection; airborne transmission; respiratory
Publication Date
Document Type
Field Studies; Hazard Evaluation and Technical Assistance
Fiscal Year
NTIS Accession No.
NTIS Price
Identifying No.
HETA-2012-0155-3180; B20130805
NIOSH Division
Priority Area
Healthcare and Social Assistance; Transportation, Warehousing and Utilities
SIC Code
Source Name
National Institute for Occupational Safety and Health