A 16-Year-Old Roofer Helper Dies After 28-Foot Fall Down an Unguarded Elevator Shaft Opening - Pennsylvania |
| ||||||||||
SummaryOn June 10, 2000, a 16-year-old roofer helper (the victim) died after falling approximately 28 feet down an unguarded elevator shaft opening. The victim's employer (the victim's father) had been subcontracted to put a roof on a two-story commercial office building under construction. On the day of the incident, the victim and his 25-year-old brother were cutting and stacking lumber for roof trusses on the second floor of the structure. To cut the lumber for trusses, the brothers were placing it on wood saw horses. They had set the saw horses up in the vicinity of a 19-foot, 7-inch by 25-foot, 2-inch unguarded elevator shaft opening in the floor. The brothers had been working cutting the lumber since 8 a.m. in the same area. At approximately 2 p.m., the older brother told the victim to pick up the scrap lumber around the saw horses and clean up the work area. The older brother then walked around one saw horse to pick up the circular saw while the victim walked around the other saw horse toward the unguarded elevator shaft. The older brother heard boards rattling and looked up and didn't see the victim. He went to the edge of the unguarded shaft opening and saw the victim lying on the dirt floor at the bottom of the elevator shaft. An employee of the prime contractor working at ground level heard a noise and looked over to see the victim lying on the ground. He ran to the victim, then to the company truck to call 911. The victim had a faint pulse and shallow breathing. When the Emergency Medical Service (EMS) responded, they attended to the victim then transported him to the hospital where he was pronounced dead. NIOSH investigators concluded that, to help prevent similar occurrences, employers should:
IntroductionOn June 10, 2000, a 16-year-old construction laborer (the victim) died after falling 28 feet down an unguarded elevator shaft. On June 14, 2000, the National Institute for Occupational Safety and Health (NIOSH), Division of Safety Research (DSR), was notified of the incident by the U.S. Department of Labor, Wage and Hour Division. On August 7, 2000, a DSR occupational safety and health specialist conducted an investigation of the incident. The incident was reviewed with the Occupational Safety and Health Administration (OSHA) compliance officer and Wage and Hour Division investigator assigned to the case. Pictures taken by the OSHA compliance officer immediately after the incident, the police report and death certificate were reviewed. The employer declined to participate in the investigation, and the investigator was denied entry to the site. The employer (victim's father) operated a roofing company that had been in business for 15 years, employing six workers at the time of the incident. The company had no written safety policies or safety program. Training for workers was provided on the job. This training was limited to roofing activities. There was no training given to employees pertaining to hazard awareness or identification. Records show that the employer had been cited by Wage and Hour 10 years ago for allowing a 15-year-old (the victim's 25-year-old brother) to operate a powered circular saw in violation of Hazardous Occupation Order number 5 which prohibits youths less than 18 years old from operating power-driven woodworking machines. The victim had worked for his father for approximately 3 years. Back to TopInvestigationThe employer had been subcontracted to install the roof on a two-story commercial office building under construction. The company had a crew of four workers on site including the victim's grandfather, two roofers (including the owner's 25-year-old son) and a roofer helper (the victim, the owner's 16-year-old son). The crew had been on site for 1 month and had completed approximately two-thirds of the roofing work. On the day of the incident, two crew members were involved in cutting lumber for the roof trusses, while the other crew members installed the trusses; however, all 4 crew members alternated the jobs of cutting wood for the trusses, installing the trusses, and applying plywood and the roofing. On the day of the incident, the two sons of the owner were involved in cutting the lumber for the roof trusses on the second floor of the structure. They had set up two wooden saw horses and were laying the lumber to be cut on the horses. The horses were placed in the vicinity of an elevator shaft opening in the floor. The opening measured 19 feet, 7 inches by 25 feet, 2 inches. The opening was unguarded and no fall protection was used by the workers. The brothers had stacked the uncut lumber for the trusses on the side of the saw horses nearest the elevator shaft opening. The cut lumber was stacked on the opposite side of the saw horses. The crew arrived at the site at 6;45 a.m. and the brothers began cutting the lumber at approximately 8 a.m. and continued to do so until their lunch break from noon until approximately 1 p.m. The brothers continued the same task after their lunch. At approximately 2 p.m., the older brother told the victim to pick up the scrap lumber around the saw horses and clean up the work area. The older brother then walked around one saw horse to pick up the circular saw while the victim walked around the other saw horse toward the unguarded elevator shaft. The older brother heard boards rattling, looked up and didn't see the victim. He went to the edge of the unguarded shaft opening and saw the victim lying on the dirt floor at the bottom of the elevator shaft. An employee of the prime contractor working at ground level heard a noise and looked over to see the victim lying on the ground. He ran to the victim, then to the company truck to call 911. The victim had a faint pulse and shallow breathing. When the Emergency Medical Service (EMS) responded, they attended to the victim with the help of police officers who had arrived at the scene. The police provided traffic support as the EMS transported the victim to the hospital where he was pronounced dead. Back to TopCause of DeathThe attending physician listed the cause of death as multiple trauma. Recommendations and DiscussionRecommendation #1: Employers should ensure that all employees are protected from falls when the potential for falls exist.Discussion: Even though the victim and his brother were exposed to the serious fall hazard of the elevator shaft, no fall protection was provided in the hazard area. Additionally, the floor opening was not covered, nor was there a guardrail system around its perimeter. Every worker exposed to a fall of over 6 feet due to the unprotected edge of a floor opening should be protected from falls by means of a guardrail system, safety net systems, or personal fall arrest systems. OSHA regulations pertaining to fall protection may be found in 29 CFR 1926.501.1 OSHA regulations pertaining to the erection of guardrail systems may be found in 29 CFR 1926.502.2
| |||||||||||