| |
|
Please Circle
|
| |
Dispensing and Use
|
| |
-
Are only approved pumps, drawing from the top of the
storage containers, used to transfer flammable liquids?
[29 CFR 1910.106(e)(2)(iv)(d) and
29 CFR 1926.152(e)(3 & 5)]
|
Y N N/A ??
|
| |
-
Are only approved self-closing valves or faucets used in
gravity transfer of flammable liquids from storage
containers? [29 CFR 1910.106(e)(2)(iv)(d) and
29 CFR 1926.152(e)(3)]
|
Y N N/A ??
|
| |
-
Is air or gas pressure prohibited for transfer of flammable
or combustible liquids unless the tank, drum or containers
has been approved as a pressure vessel?
[29 CFR 1910.106(e)(2)(iv)(d) and NFPA 30]
|
Y N N/A ??
|
| |
-
Are containers and portable tanks used for flammable
liquids electrically bonded or grounded during transfers?
[29 CFR 1926.152(e)(2) and
29 CFR1910.106(e)(3)(vi)]
|
Y N N/A ??
|
| |
-
Are leaks and spills of flammable or combustible liquids
disposed of promptly and safely?
[29 CFR 1926.152(f)(2)]
|
Y N N/A ??
|
| |
-
Are spills of flammable or combustible liquids cleaned
up promptly?
[29 CFR 1910.106(e)(9)(i)]
|
Y N N/A ??
|
| |
-
Is the use of flames or sources of ignition prohibited in
areas where flammable vapors may be present?
[NFPA 30]
Note: 29 CFR 1926.152(f)(3) requires a distance of at
least 50 feet between any source of ignition and
flammable liquids.
|
Y N N/A ??
|
| |
Storage and Use Quantities
|
| |
-
Is storage of flammable and combustible liquids limited
to that required for current activities and maintenance?
[NFPA 30]
|
Y N N/A ??
|
| |
-
Outside of approved cabinets or storage rooms, are
containers of Class I liquids limited to a capacity of
one gallon, or two gallons, if safety cans are used?
[NFPA 30: 4-5.5.2]
|
Y N N/A ??
|
| |
-
Are fewer than 10 gallons of Class I and Class II liquids
stored outside of an approved storage cabinet or interior
storage room (except in safety cans)?
[NFPA 30 4-5.5.3]
|
Y N N/A ??
|
| |
-
Are fewer than 25 gallons of flammable liquids stored in
safety cans outside of an approved storage cabinet or
interior storage room?
[NFPA 30: 4-5.5.4 and 29 CFR 1926.152(b)(1)]
|
Y N N/A ??
|
| |
-
Are fewer than 60 gallons of Class IIIA liquids stored outside
of an approved storage cabinet or interior storage room?
[NFPA 30 4-5.5.5]
Note: OSHA under 29 CFR 1926.152(b)(1) does not permit
more than 25 gallons of combustible liquids stored outside
of an approved storage cabinet or interior storage room.
|
Y N N/A ??
|
| |
Design and Capacity of Containers
|
| |
-
Are only approved containers used for storing flammable
or combustible liquids?
[29 CFR 1910.106(d)(2)(i)]
Note: All gasoline must be stored in approved containers.
|
Y N N/A ??
|
| |
-
Are flammable and combustible liquid containers stored
in accordance with the requirements of Table 1?
[29 CFR 1910.106(d)(2)(iii)]
|
Y N N/A ??
|
| |
|
Table 1: Maximum Allowable Size of Containers and Portable Tanks
|
|
Container Type*
|
Flammable Liquids
|
Combustible liquids
|
Glass or approved plastic
Metal (other than DOT drums)
Safety cans
Metal drums (DOT specifications)
Approved portable tanks
|
| Class IA |
Class IB |
Class IC |
1 pt
1 gal
2 gal
60 gal
660 gal |
1 pt
5 gal
5 gal
60 gal
660 gal
|
1 gal
5 gal
5 gal
60 gal
660 gal |
|
| Class II |
Class III |
1 gal
5 gal
5 gal
60 gal
660 gal |
1 gal
5 gal
5 gal
60 gal
660 gal |
|
*Note: Container exemptions: medicines, beverages,
foodstuffs, cosmetics, and other
common consumer items, when packaged according to commonly accepted practices.
|
| |
Design, Contruction, and Capacity
of Storage Cabinets
|
| |
-
Is storage in cabinets restricted to not more than 60 gallons
of Class I or Class II liquids and not more than 120 gallons
of Class III liquids?
[29 CFR 1910.106(d)(3)(i) and
29 CFR 1926.152(b)(3)]
|
Y N N/A ??
|
| |
-
Are all cabinets labeled in conspicuous lettering:
"FLAMMABLE-KEEP FIRE AWAY"?
[29 CFR 1910.106(d)(3)(ii) and 29 CFR 1926.152(b)(2)(iii)]
|
Y N N/A ??
|
| |
-
Are metal cabinets constructed so that the top, sides
and door are at least #18 gauge sheet iron and double
spaced wall with 1-1/2 inch air space?
[29 CFR 1910.106(d)(3)(ii)(a)]
|
Y N N/A ??
|
| |
-
Is the door provided with a three point lock and a sill
raised at least 2 inches above the bottom of the cabinet?
[29 CFR 1910.106(d)(3)(ii)(a)]
|
Y N N/A ??
|
| |
-
Are wooden cabinets constructed so that the bottom, sides
and top are of approved grade plywood at least 1 inch thick?
[29 CFR 1910.106(d)(3)(ii)(b) and
29 CFR 1926.152(b)(2)(I)]
|
Y N N/A ??
|
| |
-
Are all wooden cabinet joints rabbetted and fastened
in two directions with flat head wood screws?
[29 CFR 1910.106(d)(3)(ii)(b) and
29 CFR 1926.152(b)(2)(I)]
|
Y N N/A ??
|
| |
-
When more than one door is used on wooden cabinets,
is there a rabbetted overlap of not less than 1 inch?
[29 CFR 1910.106(d)(3)(ii)(b) and
29 CFR 1926.152(b)(2)(I)]
|
Y N N/A ??
|
| |
-
Are no more than three (3) cabinets located in one fire area?
[NFPA 30]
|
Y N N/A ??
|
| |
-
Are cabinet vents sealed unless vented to the outdoors?
[NFPA 30]
|
Y N N/A ??
|
| |
Design and Construction of Inside Storage Rooms
|
| |
-
Are openings to other rooms or buildings from
flammable/combustible liquids storage rooms provided
with a noncombustible liquid-tight raised sill or ramp
at least 4 inches in height?
[29 CFR 1910.106(d)(4)(i) and
29 CFR 1926.152(b)(4)(ii)]
Note: Alternatively, the floor of the storage area shall
be at least 4 inches below the surrounding floor.
|
Y N N/A ??
|
| |
-
Are openings to storage rooms provided with
approved self-closing fire doors?
[29 CFR 1910.106(d)(4)(i) and
29 CFR 1926.152(b)(4)(ii)]
|
Y N N/A ??
|
 |
-
Does storage in inside rooms comply with the requirements
of Table 2?
[29 CFR 1910.106(d)(4)(ii) and 29 CFR 1926.152(b)(4)(iv)]
|
Y N N/A ??
|
| |
|
Table 2: Storage in Inside Rooms
|
Fire Protection
Provided1
|
Fire
Resistance
|
Maximum
Size
|
Total Allowable
Quantities2
|
Yes
No
Yes
No
|
2 hours
2 hours
1 hour
1 hour
|
500 sq. ft.
500 sq. ft.
150 sq. ft.
150 sq. ft.
|
10
5
4
2
|
1Fire protection system shall be sprinkler, water spray,
carbon dioxide, or other system.
2(gals/sq. ft/floor area)
|
| |
-
Is the room liquid tight where the wall joins the floor?
[29 CFR 1910.106(d)(4)(i) and
29 CFR 1926.152(b)(4)(ii)]
Note: A permissible alternative to the sill or ramp is an
open-grated trench inside the room which drains to
a safe location.
|
Y N N/A ??
|
 |
-
Is the electrical wiring and equipment located inside the
storage room especially designed to prevent possible
ignition of any released flammable vapors?
[29 CFR 1910.106(d)(4)(iii) and 29
CFR 1926.152(d)(d)(v)]
Note: Anything which looks like normal household wiring
including switches, plugs, lighting or any normal
equipment such as radios are not permitted.
|
Y N N/A ??
|
| |
-
Is every inside storage room provided with either a
gravity or mechanical exhaust ventilation system?
[29 CFR 1910.106(d)(4)(iv) and
29 CFR 1926.152(b)(4)(vi)]
|
Y N N/A ??
|
| |
-
Does the ventilation system have an exhaust not more
than 12 inches off the floor?
[29 CFR 1926.152(b)(4)(vi)]
|
Y N N/A ??
|
 |
-
Does the ventilation system provide for a complete
change of air within the room at least six times
per hour?
[29 CFR 1910.106(d)(4)(iv) and
29 CFR 1926.152(b)(4)(vi)]
|
Y N N/A ??
|
| |
-
If a mechanical exhaust system is used, is the switch
located outside of the door?
[29 CFR 1910.106(d)(4)(iv) and
29 CFR 1926.152(b)(4)(vi)]
|
Y N N/A ??
|
| |
-
Are ventilation equipment and the lighting fixtures
operated by the same switch?
[29 CFR 1910.106(d)(4)(iv) and
29 CFR 1926.152(b)(4)(vi)]
|
Y N N/A ??
|
| |
-
When gravity ventilation is provided, are the fresh air
intake as well as the exhaust outlet from the room
located on the exterior of the building in which the
room is located?
[29 CFR 1910.106(d)(4)(iv) and
29 CFR 1926.152(b)(4)(vi)]
|
Y N N/A ??
|
| |
-
Is there a 3 foot wide clearance in the aisle in every
storage room?
[29 CFR 1910.106(d)(4)(v)]
|
Y N N/A ??
|
| |
-
Is stacking of 30 gallon capacity containers prohibited?
[29 CFR 1910.106(d)(4)(v)]
|
Y N N/A ??
|
| |
General Storage Inside and Outside Buildings
|
| |
-
Is the storage of flammable or combustible liquids
prohibited near exits, stairways, or areas normally
used for the safe exit of people?
[29 CFR 1910.106(d)(5)(I)]
|
Y N N/A ??
|
| |
-
Is the storage of flammable or combustible liquids
prohibited in office areas except that required for
maintenance and operation of building and
operation of equipment?
[29 CFR 1910.106(d)(5)(iii)]
Note: Permitted materials shall be stored in safety cans,
in closed metal containers inside storage cabinets, or
in an inside storage room that does not open into public
areas of the building.
|
Y N N/A ??
|
| |
-
Are portable fire extinguishers available at locations where
flammable or combustible liquids are stored?
[29 CFR 1910.106(d)(7) and
29 CFR 1926.152(d)(1)]
Note: OSHA requires that at least one portable fire
extinguisher having a rating of not less than 20-B units
be located not less than 25 feet, nor more than 75 feet,
from any flammable liquid storage area located outside.
|
Y N N/A ??
|
| |
-
Are containers of flammable and combustible liquids
closed when not in use?
[29 CFR 1910.106(e)(2)(ii) and
29 CFR 1926.152(f)(1)]
|
Y N N/A ??
|
| |
-
Are combustible waste materials and residues kept to a
minimum, stored in covered metal receptacles,
and disposed of daily?
[29 CFR 1910.106(e)(9)(iii)]
|
Y N N/A ??
|
| |
-
Are flammable and combustible liquids stored in their
original container or in an approved safety can?
[NFPA 30]
|
Y N N/A ??
|
| |
-
Unless the original container is designed to be used, are
flammable or combustible liquids transferred to
an approved safety can prior to use?
[NFPA 30]
|
Y N N/A ??
|
| |
-
Are open flames and smoking prohibited in flammable or
combustible liquids storage areas?
[29 CFR 1910.106(d)(7)(iii)]
|
Y N N/A ??
|
| |
-
Are storage areas for flammable or combustible liquids
kept free from combustible materials?
[29 CFR 1910.106(d)(iv)]
|
Y N N/A ??
|