|
|
| Name of school: |
| Date of inspection: |
| Career-Technical program/course/room: |
| Signature of inspector: |
![]() |
General
Fire Requirements
Self-Inspection Checklist |
![]()
Guidelines: This checklist covers regulations from the U.S. Department of Labor, Occupational Safety and Health Administration (OSHA), general industry standards 29 CFR 1910.36, 1910.38, and 1910.159. The regulations cited apply only to private employers and their employees, unless adopted by a State agency and applied to other groups such as public employees. Recommendations from the National Fire Protection Association (NFPA) standards have also been included.
| Please Circle | |
stairways, doors, and other exits are in proper working condition? [NFPA 1] |
Y N N/A ?? |
[29 CFR 1910.36(b)(4)] Note:
Exit doors must not be locked, barred, or blocked
|
Y N N/A ?? |
[NFPA 101] |
Y N N/A ?? |
free of obstructions that would interfere with the evacuation of the building or the operation of the fire department? [29 CFR 1910.36(d)(1)] |
Y N N/A ?? |
condition? [NFPA 80] |
Y N N/A ?? |
|
Y N N/A ?? |
contribute to the spread of fire from one room to another repaired? [NFPA 101] |
Y N N/A ?? |
material below (such as head deflectors) at least 18 inches? [29 CFR 1910.159(c)(10)] |
Y N N/A ?? |
materials and residues removed so that they will not contribute to a fire? [29 CFR 1910.38(b)(3)] Note:
Examples of violations include open boxes of papers
|
Y N N/A ?? |
and light fixtures to prevent possible ignition? [NFPA 231] |
Y N N/A ?? |
radiant space heaters, furnace ducts, and flues not less than three feet in all directions or in accordance with the clearances shown on the approval agency label? [NFPA 231] |
Y N N/A ?? |
flammable character prohibited? [NFPA 101] |
Y N N/A ?? |
streamers, and fabrics flame resistant? [NFPA 101] |
Y N N/A ?? |
less of the wall area? [NFPA 1] |
Y N N/A ?? |
![]()
Comments/Corrective action:
|
|
|
|