Underground
Storage Tanks
(UST) Self-Inspection Checklist |
![]()
Guidelines: This checklists covers regulations issued by the U.S. Environmental Protection Agency (EPA) under 40 CFR 280. The purpose of these regulations is to reduce the likelihood of leaks of hazardous substances from these tanks into soil and ground water and to ensure timely detection and abatement of such releases. A yes answer to a question indicates that this portion of the inspection complies with the OSHA or EPA standard, or with a nonregulatory recommendation.
Questions marked with this symbol may require the help of an outside expert.
The regulations require registration and specific spill and leak prevention measures based on the type of UST, age of the tank, and substances stored in the tank system. USTs are any one or combination of tanks (including underground pipes connected to them) used to contain an accumulation of regulated substances. Regulated substances include petroleum products (e.g., gasoline and used motor oil) and certain other hazardous substances. Heating oil if stored and used on the premises is not covered by the Federal regulations.
States typically enforce the Federal regulations as well as adopt their own regulations for USTs. Please consult the appropriate agency in your state about any additional regulations and requirements. This checklist includes some recommended practices that are based on regulations adopted in the State of New Jersey.
| Please Circle | ||
| Registration | ||
in your State with the appropriate State agency? [40 CFR 280.22] |
Y N N/A ?? |
|
| Performance Standards and Engineering Requirements | ||
|
|
installed on all existing USTs? [40 CFR 280.21] |
Y N N/A ?? |
|
|
for new USTs that will be installed? [40 CFR 280.20] |
Y N N/A ?? |
|
|
all USTs? [40 CFR 280.40; 280.41 and 280.42] Note:
Acceptable leak detection methods include at
|
Y N N/A ?? |
| Spill and Overfill Control | ||
not overfilled during delivery? Do procedures include methods to measure available tank volume and to meter delivery volume immediately before delivery? [40 CFR 280.30] |
Y N N/A ?? |
|
| Release Response Plan | ||
at the school that includes the following items? [recommended] State officials. charge of the school during the emergency. contractor(s). leak from the UST. |
Y N N/A ?? |
|
| Release Reporting, Investigation, and Cleanup | ||
that may indicate a leak? [recommended] material soil, surface water, or adjacent well condensation levels |
Y N N/A ?? |
|
|
|
is a plan available to investigate the condition that includes the items listed below? [40 CFR 280.50 and 280.52] using appropriate methods |
Y N N/A ?? |
|
|
followed that includes the items listed below? [40 CFR 280.61 through 280.66] findings in a report. water, and other affected media. |
Y N N/A ?? |
| Other Requirements | ||
|
|
protection operated and maintained to provide continuous corrosion protection? [40 CFR 280.31] |
Y N N/A ?? |
only by qualified persons? [40 CFR 280.20 and 280.33] |
Y N N/A ?? |
|
|
|
requirements placed out of service and closed according to Federal and State procedures? [40 CFR 280.21 and 280.70 through 280.74] |
Y N N/A ?? |
![]()
Comments/Corrective action:
|
|
|
|